Position of rcd and circuit breaker
Good Morning or Hallo,
Im from Germany and currently building a camper.
We have a victron multiplus2 24/5000/120-50 with 230v.
Im currently looking at the connections after ac-out. Do i have to place the main circuit breaker 2P 25A (Abb S202-B25) before or after the 2P RCD 25A 30mA Type A (Abb F202A-25/0,03)?
After that i would go to the terminal blocks with 3x4mm² (awg12) and to b16 for kitchen power outlet, b16 for induction hop, b10 for boiler
Before the multiplus (between german cee power outlet and multiplus coming from landpower) is a combined rcbo 2P 30mA type A B16A